1YHT530004D05 D
4.1.4.11
4.1.5
4.1.5.1
615 series
Technical Manual
Technical data
Table 229:
DPH3xPDOC Technical data
Characteristic
Operation
DPH3LPDOC
accuracy
DPH3HPDOC
1)2)
Start time
I
= 2 x set
Fault
Start value
Reset time
Reset ratio
Retardation time
Operate time accuracy in definite time
mode
Operate time accuracy in inverse time
mode
Suppression of harmonics
Measurement mode and Pol quantity = default, current before fault = 0.0 x I
1)
1.0 x U
, f
= 50 Hz, fault current in one phase with nominal frequency injected from random phase
n
n
angle, results based on statistical distribution of 1000 measurements.
2) Includes the delay of the signal output contact.
3) Maximum
Start value = 2.5 x I
Three-phase thermal protection for feeders, cables and
distribution transformers T1PTTR
Identification
Function description
Three-phase thermal protection for
feeders, cables and distribution
transformers
Value
Depending on the frequency of the current measured: f
Hz
Current: ±1.5% of the set value or ±0.002 x I
Voltage: ±1.5% of the set value or ±0.002 x U
Phase angle: ±2°
±1.5% of set value or ±0.002 x I
of 0.1...10 x I
)
n
±5.0% of the set value (at currents in the range of 10...40 x
I
)
n
Voltage: ±1.5% of the set value or ±0.002 x U
Phase angle: ±2°
Minimum
38 ms
< 40 ms
Typical 0.96
< 35 ms
±1.0% of the set value or ±20 ms
±5.0% of the theoretical value or ±20 ms
RMS: No suppression
DFT: -50 dB at f = n x f
Peak-to-Peak: No suppression
Peak-to-Peak + backup: No suppression
,
Start value multiples in range of 1.5 to 20.
n
IEC 61850
identification
T1PTTR
Section 4
Protection functions
n
n
(at currents in the range
n
n
Typical
Maximum
40 ms
43 ms
3)
, where n = 2, 3, 4, 5,...
n
, voltage before fault =
n
IEC 60617
ANSI/IEEE C37.2
identification
device number
3lth>
49F
±2
n
225