290/341
Bosch Rexroth AG
Cables, accessories, additional components
8.3

Additional components

8.3.1
Transformers
General information
Grounded mains
Ungrounded mains
Autotransformers for drive controllers
Short type designation 1 2 3 4 5 6 7 8 9
Example:
T R A F O
Object:
TRAFO = transformer
Product:
DST = AC autotransformer
Nominal power:
■2,00 = 2.0 kVA
■2,50 = 2.5 kVA
■4,00 = 4.0 kVA
■5,00 = 5.0 kVA
■7,50 = 7.5 kVA
Type of construction (design):
S = upright mounting
Nominal input voltage (phase-phase):
e.g., 380,415,440 = AC 380 V, AC 415 V, AC 440 V
Nominal output voltage (phase-phase):
e.g., 220 = 230 V
Special design:
e.g., 10MM = maximum conductor connection cross section 10 mm
Transformers are only needed when the mains voltage is outside of the al‐
lowed nominal voltage of the drive controller.
For grounded mains, the mains voltage is adjusted to the nominal voltage of
the device by means of autotransformers which have been sized for a specif‐
ic output voltage range.
For voltage adjustment of ungrounded mains, always connect isolating trans‐
formers to prevent overvoltages between outer conductor and ground.
Types
1
0 1 2 3 4 5 6 7 8 9
D S T
■ 4 , 0 0 / S / 3 8 0 , 4 1 5 , 4 4 0 - 2 2 0
Tab. 8-23:
DST, type code
DOK-INDRV*-HCS01******-PR05-EN-P
Rexroth IndraDrive CsDrive Systems with HCS01
2
0 1 2 3 4 5 6 7 8 9
2
3
4
0 1 2 3 4 5 6 7 8 9
0
1 0 M M