BATTERY TEST.
The battery test certifies that the
backup
capability of the power supply is functioning normally.
The sys-
tem must be halted before performing this test.
Proceed as fol-
lows:
a.
On rear panel of the power supply, momentarily press the BAT-
TERY TEST
toggle switch.
The CROWBAR/BATT. TEST
indicator
should light and the BATTERY STATUS indicator should flash at
a 2-Hz rate.
Allow the battery to
discharge
for three
to
five min utes.
b.
Return the power
supply to normal operation by
pressing the
RESET pushbuton on power supply front panel.
c.
The BATTERY STATUS
indicator flashes at a O.5-Hz
rate until
the battery is fully charged. Then,the indicator remains con-
tinually lighted.
9-24. HP 30311A Adjustments
The following
adjustments should be performed after replacing
a
power supply
or after replacing a circuit board or
battery pack
within the power supply.
9-25.
BATTERY (FLOAT) VOLTAGE ADJUSTMENT.
Float voltage must be
adj usted whenever a battery pack is replaced.
I
CAUTION
I
The replacement battery pack
must
be
at
a
stable
known
ambient temperature before the
adjustment is performed.
For
a
change
in
ambient
temperature,
the
settling time for
the pack is four to six
hours.
Failure
to
observe
this precaution may considerably de-
grade the backup time and/or shorten the life
of the battery pack.
Adjust the float voltage as follows:
a.
Power down the
system by placing the corresponding
UPPER or
LOWER MEMORY DC POWER sw itch on the System
Dc
Control
Panel
to STANDBY and place the corresponding HP 303llA Power Supply
power switch off (down).
b.
Remove the power supply from the cabinet and place on a suit-
able s uppor t.
c.
Remove the top cover from the power supply.
9-16