13.2 Fundamentals
13.2.9.2

Calling Support information

Using the footer of the web server, you can call up the support addresses for SINAMICS S120.
1. Click "Support" in the footer of the web server.
The following information is shown:
Figure 13-9
You can use the links to open or copy the desired support addresses.
2. Click "OK" in order to close the "Support" dialog.
13.2.9.3

Saving data in a non-volatile fashion

Changed settings are saved in the volatile memory of the converter, and retained when the web
server is closed. The settings are lost when the drive is switched off.
For this reason, it is important that you store the changes regularly in a power-independent
manner (also known as "Copy RAM to ROM"). You can either save the setting for each
individual commissioning step or save all the settings made and the tuning results at the end of
the commissioning.
1. To save powerfail-proof, click
A save prompt appears:
Figure 13-10
2. Click "Save".
You have now saved the data in power-independent memory.
730
Support addresses
in the footer of the web server.
Permanent saving prompt
Function Manual, 06/2019, 6SL3097-5AB00-0BP2
Drive functions