Siemens SINAMICS S120 Function Manual page 251

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

The speed controller is set to the symmetrical optimum in accordance with dynamic factor
p1967. Parameter p1967 must be set before the optimization run and only affects the
calculation of the controller parameters. If, during the measurement, it becomes clear that, with
the specified dynamic factor, the drive cannot operate in a stable manner or the torque ripples
are too large, the dynamic response is reduced automatically and the result displayed in r1968.
In this case, a check must be performed to see whether the drive is running stable across the
entire setting range. The dynamic response might need to be reduced or the Kp_n/Tn_n
adaptation for the speed controller parameterized accordingly.
Note
Dynamic response reduced too much
If the dynamic response of the speed controller is reduced excessively because of load
oscillations, the oscillation test can also be deactivated (p1959.4 = 0).
Recommendations
● Induction motors
When commissioning induction machines, you are advised to proceed as follows:
– Before connecting the load, a complete "rotating measurement" (p1900 = 3 or without
– When the load is connected, speed controller tuning should be repeated because the
● Permanent-magnet synchronous motors
When permanent-magnet synchronous motors are commissioned, the speed controller
should be tuned (p1900 = 3 or p1960 > 0) when the load is connected.
Procedure
Unexpected motor motion during motor data identification
Motor movement caused when optimizing the speed controller can result in death, severe
injury or material damage.
● Ensure that nobody is in the danger zone and that the mechanical parts can move freely.
Drive functions
Function Manual, 06/2019, 6SL3097-5AB00-0BP2
encoder: p1960 = 1; with encoder: p1960 = 2) should be carried out. Since the induction
machine is idling, you can expect highly accurate results for the saturation characteristic
and the rated magnetizing current.
total moment of inertia has changed. This is realized by selecting parameter p1960
(without encoder: p1960 = 3; with encoder: p1960 = 4). During the speed optimization,
the saturation characteristic recording is automatically deactivated in parameter p1959.
WARNING
6.13 Motor data identification and rotating measurement
Vector control
249

Advertisement

Table of Contents
loading

Table of Contents