Function description
The function is used to automatically shift a selected current setpoint filter to a mechanical
resonant frequency. Detailed descriptions on the principle of operation of the current setpoint
filter adaptation as well all of the parameters that are linked with the adaptation can be found
later in this chapter.
Enabling the function
The function is activated for S120 drives together with the "Moment of inertia estimator
(Page 540)" function module.
Activating/deactivating current setpoint filter adaption
Active/deactivate the current setpoint filter adaptation via parameter p5280. The following
settings are possible:
Setting
-1
0
1
Note
The current setpoint filters 1 to 4 are activated by default. The extended current setpoint filters
5 to 10 can be activated additionally (see chapter "Current setpoint filter (Page 100)").
Further parameters of the current setpoint filter adaptation and their purpose:
p5281
p5282
p5283
p5284
p5285
Drive functions
Function Manual, 06/2019, 6SL3097-5AB00-0BP2
Explanation
The "Current setpoint filter adaptation" function is deactivated together with the assigned filter
(see p5281).
With this setting, not only the adaptation, but also an assigned filter is deactivated. The
associated bit is automatically deleted in parameters p1656 and p5200. However, the filter is
not reset in its characteristic, it retains the values saved last. In contrast, the adaptation
parameter is automatically reset to 0.
The "Current setpoint filter adaptation" function is inactive.
The adaptation is deactivate with this setting. However, a filter assigned to the adaptation can
still be active. The filter function is not affected by this setting.
The "Current setpoint filter adaptation" function is permanently active.
A mechanical resonant frequency is determined with this activation and the appropriate
blocking frequency is set automatically. If the band-stop filter has not been activated yet (see
parameter p1656 or p5200), it is activated automatically.
While the function generator generates a signal with the "noise" signal shape (p4820 = 4), the
adaptation is temporarily inactive.
Specifies which of the current setpoint filters is to be used for the adaptation.
Defines the lower limit frequency.
Defines the upper limit frequency.
Defines the activation threshold of the adaptation.
Shows the current blocking frequency.
Servo control
5.9 Autotuning
121