Basic functions
8.7 dv/dt filter plus Voltage Peak Limiter
The maximum permissible pulse frequency when using a du/dt filter:
● For 2.5 kHz
– Chassis power units from 315 kW to 800 kW at 400 V
– Chassis power units from 75 kW to 1200 kW at 690 V
– Chassis-2 power units at 400 V
● For 4 kHz
– Chassis power units up to 250 kW at 400 V
Configuring the function
The dv/dt filter must be activated when commissioning the system (p0230 = 2).
322
Function Manual, 06/2019, 6SL3097-5AB00-0BP2