12.Compare the deflection at the starting point of the measurement (2) with the deflection at the
end point of the measurement (3).
The following figure shows the measurement result. A guide line (1) is shown for the optical
alignment and aligned as reference line at the starting point (2) of the measurement.
Figure 5-22
– Result 1: You have set parameter p3096[0] correctly when the deflection at the starting
– Result 2: The holding brake is not strong enough when the deflection at the starting point
The following figure shows an example of the signal curve of the deflection when the brake
is too weak.
Drive functions
Function Manual, 06/2019, 6SL3097-5AB00-0BP2
Signal (red/top): Measuring current
Signal (blue/bottom): Deflection
Guide line
Starting point of the measurement
End point of the measurement
Amplitudes of measuring currents 1 to 12 (p3093)
Measurement result: Determined deflection
point of the measurement (2) corresponds to the deflection at the end point of the
measurement (3).
of the measurement (2) differs significantly from the deflection at the end point of the
measurement (3). In this case, we recommend that you reduce the measuring current
step-by-step until the deflection at the starting point of the measurement corresponds to
the deflection at the end point of the measurement, or approximately. Only continue with
the next step when this has been ensured.
Servo control
5.16 Pole position identification
159