Basic functions
8.21 Tolerant encoder monitoring
Commissioning the function
Carry out the following steps to start the function:
1. Enter the value "0" (edge time measurement) in parameter p0430.20 for the sliding mean
value generation.
2. In parameter p4685, enter the number of current controller cycles over which the average
value should be formed to calculate the speed.
The averaging means that individual incorrect pulses, depending on the number of specified
cycles, are smoothed.
8.21.12

Troubleshooting

Overview
The table below gives you an overview of the error patterns and their possible causes.
Table 8-9
Fault profile
378
Fault profiles and their possible causes
Fault description
No fault
F3x101 (zero mark
failed)
Function Manual, 06/2019, 6SL3097-5AB00-0BP2
Remedy
Check that the connec‐
tion assignment is cor‐
rect (A interchanged with
–A or B interchanged
with –B)
Drive functions