Commissioning U/f control
Before commissioning the U/f control, observe the following information:
Note
The run-up at the current limit (p0640) permits a quick run-up of the drive, e.g. when operating
the drive with variable moments of inertia. Only the ramp-function generator stops when the
current limit (p0640) is reached. This does not prevent the current from increasing even further.
In view of this, the parameters you assign must include a safety margin relative to the current
limits for the monitoring functions to prevent the drive from switching off with an overcurrent
fault.
To commission the U/f control, proceed as follows:
1. Check the requirements for U/f control.
– Initial commissioning has been performed:
– Initial commissioning has not been performed:
2. Set the rated motor speed via parameter p0311.
3. Activate U/f control with the parameter setting of p1317 = 1.
Note
Automatic activation of additional functions
With p1317 = 1, the following functions are also activated automatically:
● Resonance damping (p1338)
● Vdc controller (p1240, p1244, p1248, p1250)
● Limitation of the up ramp as a result of M, P and I limits
● The ramp-function generator is stopped as soon as the current limit p0640 is exceeded.
4. Issue the enable signals for operation.
5. Enter the speed setpoint.
Drive functions
Function Manual, 06/2019, 6SL3097-5AB00-0BP2
The parameters for U/f control have been preset with appropriate values.
The following relevant motor data must be checked and corrected:
r0313 Motor pole pair number, actual (or calculated)
p0314 motor pole pair number
p1318 U/f control ramp-up/ramp-down time
p1319 U/f control voltage at zero frequency
p1326 U/f control programmable characteristic frequency 4
p1327 U/f control programmable characteristic voltage 4
p1338[0...n] U/f mode resonance damping gain
p1339[0...n] U/f mode resonance damping filter time constant
p1349[0...n] U/f mode resonance damping maximum frequency
In order to obtain a pure diagnostic mode without any influence on actual values, the
resonance damping must be deactivated (p1338 = 0).
Servo control
5.12 U/f control
133