Connection For Using General-Purpose Stabilized Power Supply - Mitsubishi Electric MELDAS 600 Series Connection Manual

Hide thumbs Also See for MELDAS 600 Series:
Table of Contents

Advertisement

4.3.2 Connection for Using General-purpose Stabilized Power Supply

A general-purpose stabilized power supply is used with the M6 Series (M610/630) not provided with a
hard disk.
(1) General-purpose stabilized power supply connection
R S T
NF B
1. Refer to section "4.2.2 Control unit connector pin assignment" for details on the control unit's
DCIN connection.
2. Leave CF01 on the control unit open.
WARNING
Do not damage, apply excessive stress, place heavy things on or sandwich the cables, as
this may lead to electric shocks.
(2) Power supply specification
Control unit power specifications
Output voltage
Ripple
Output current
Caution) Prepare a control unit power supply (general-purpose stabilized power supply) separate
from the base I/O and remote I/O unit power supply.
CHAPTER 4 SYSTEM CONNECTION
4.3 Connection of Power Supply
MC2
MC2
MC2
MC f or ON/OFF
NF B
+24V±5%
±5% (P-P)
3A
Display unit
ON
OFF
Control unit
power
General- purpose stabilized
power supply
MC2 (ON/OFF MC) specifications
Contact rating
Operation coil
No. of contacts
Standards
30
Control unit
DCIN
250VAC/1 A or more
250VAC/0.2 A or less
3a or more
VDE Standards