3.3.2 Shield Clamping of Cables

The shield cable connected to the control unit, servo amplifier and spindle amplifier must be connected
to the grounding plate to stabilize operation while preventing malfunctioning due to noise.
The shield can be connected to the grounding plate with lead wires, with clamp fittings or with the
connector GNP plate. Refer to the following drawings to treat the shield cable.
Lead wire treatment method
Lead wire treatment
method
Fold the cable shield over the sheath, and wrap copper foil tape around it. Connect the wound
copper foil tape to the connector's GND plate.
(1) Peel part of the cable sheath and expose the shield as
shown in the drawing.
Press the exposed part against the grounding plate with
the cable clamp fittings.
(2) If the cable is thin, clamp several together in a bunch.
(3) Use adequate force when tightening the cable so that
the wire material is not damaged.
(4) Connect each grounding plate together and ground
them at one point.
Refer to APPENDIX 1 about the outline drawing of clamp fittings and grounding plate.
CHAPTER 3 INSTALLATION
3.3 Noise Countermeasures
Example of connection with lead wire
Solderin g
Shield
Cable
Example of connection with connector GND plate
Shield
GND plate
Example of connection with clamp fitting
Shield
Cable
Clamp fitting
Cable
Lead wire
Cable
Grounding plate
Cable
Less than 0.8m
12
Unit
Unit
Shield
Clamp
fitting
Grounding