6.1 Shield Clamp Fitting

The ground can be directly connected to the grounding plate to increase the effect.
Install the grounding plate near the outlet (within 10cm) of each panel, and press against the grounding
plate with the clamp fitting. If the cables are thin, several can be bundled and clamped together.
To provide sufficient frame grounding, install the grounding plate directly on the cabinet or connect with
a grounding wire.
If the grounding plate and clamp fitting set (AERSBA- SET) is required, please contact Mitsubishi.
• Outline drawing
Grounding plate
2- φ 5 hole
Installation hole
Note 1) M4 screw
AERSBAN-DSET
AERSBAN-ESET
APPENDIX 3 EMC INSTALLATION GUIDELINES
6. Parts for EMC Measures
Clamp fitting
(F itting A, B)
Clamp section drawing
17.5
6
22
35
Note 1) Screw hole for wiring to cabinet's grounding plate.
Note 2) The grounding plate thickness is 1.6mm.
A
B
C
Enclosed fitting
100
86
30
Two A clamp fittings
70
56
One B clamp fitting
Peel the cable sheath
at the clamp section
Grounding plate
129
Cable
Cable
Shield sheath
Clamp fitting
MAX L
10
Unit: mm
A clamp fitting
B clamp fitting
L
70
45