6.5 Outline of Digital Signal Output Circuit

The digital signal output circuit uses a sink type (DX4
2
1). Use within the specification ranges shown below.
Output circuit
(Machine side)
+24VDC
Output conditions
Insulation method
Rated load voltage
Max. output current
Output delay time
∗ When using an inductive load such as a relay, always connect a diode (voltage
resistance 100 V or more, 100 mA or more) in parallel to the load.
∗ When using a capacity load such as a lamp, always connect a protective resistor
(R=150Ω) serially to the load to suppress rush currents. (Make sure that the
current is less than the above tolerable current including the momentary current.)
CAUTION
When using an inductive load such as a relay, always connect a diode in parallel to the
load.
When using a capacity load such as a ramp, always connect a protective resistor serially
to the load to suppress rush currents.
CHAPTER 6 CONNECTION OF REMOTE I/O UNIT
6.5 Outline of Digital Signal Output Circuit
DO-L/DO-R
RA
R
PL
DO-L/DO-R
(Machine side)
RA
R
PL
<CAUTION >
0, 3
0, 2
0) or source type (DX4
Control
circuit
Sink type (DX2 0)
(DX3 0)
(DX4 0)
+24VDC
Control
circuit
Source type (DX2 1)
(DX3 1)
(DX4 1)
Non-insulation
+24VDC
60mA
40µs
78
1, 3