(5) Digital input (CF31)
A sink type input circuit corresponding to the machine side sink output, and a source type input
circuit corresponding to the machine side source output are shown below.
Sink type
(Machine side)
CF30
GND
GND
+24V
COM
Input conditions
Use the input signal within the following condition ranges.
1
Input voltage when external contact is ON
2
Input current when external contact is ON
3
Input voltage when external contact is OFF
4
Input current when external contact is OFF
5
Tolerable chattering time
6
Input signal hold time
7
Input circuit operation delay time
8
Machine side contact capacity
CAUTION
Do not apply voltages other than those indicated in this manual on the connector. Doing
so may lead to destruction or damage.
Input signal hold time: 40 ms or more is the guideline, and if not held for longer
than the ladder processing cycle time, the input signal will not be recognized.
T1
External sign al
+24V
Internal signal
+5V
T3
CHAPTER 5 CONNECTION OF I/O INTERFACE
5.4 Scan I/O
HR347
2.2k
2.2k
Control
circu it
T2
T1
T4
Source type
(Machine side)
CF30
+24V
COM
GND
Sink type
6V or less
9mA or more
20V or more
2mA or less
3ms or less (Refer to T1 below)
40ms or more (Refer to T2 below)
3ms ≤ T3
+30V or more, 16mA or more
T1
T3
71
HR357
2.2k
2.2k
Control
circu it
Source type
18V or more
4V or less
.
=
T4 ≤ 20ms
.
T2
T1
T4