Chapter 4 Temperature Input Module Replacement; List Of Temperature Input Module Alternative Models For Replacement - Mitsubishi Electric MELSEC-A/QnA Series Handbook

Table of Contents

Advertisement

4
TEMPERATURE INPUT MODULE REPLACEMENT
4

4.1 List of Temperature Input Module Alternative Models for Replacement

Production discontinuation
Product
Model
*1
A616TD
A60MXT(N)
Temperature
input module
A68RD3N
A68RD4N
4
- 1
TEMPERATURE INPUT MODULE
4
REPLACEMENT
Model
1) External wiring
2) Number of slots
Q64TD
3) Program
4) Performance specifications change: 4CH/module
5) Functional specifications: Not changed
1) External wiring
2) Number of slots
Q68TD-G-H02
3) Program
Q68TD-G-H01
4) Performance specifications change: 8CH/module
5) Functional specifications: The disconnection detection function is equipped (only in the
1) External wiring
2) Number of slots:
3) Program
Q64RD
4) Performance specifications change: 4CH/module
5) Functional specifications: Not changed
1) External wiring
2) Number of slots
3) Program
Q64RD-G
4) Performance specifications change: 4CH/module
5) Functional specifications: RTD Ni100-compliant and transformer isolation is provided
1) External wiring
2) Number of slots
3) Program
Q68RD3-G
4) Performance specifications change: Resolution and conversion speed
5) Functional specifications: 32-bit output is not available. RTD Ni100-compliant and
1) External wiring
2) Number of slots
3) Program
Q64RD
4) Performance specifications change: 4CH/module
5) Functional specifications: Not changed
1) External wiring
2) Number of slots
3) Program
Q64RD-G
4) Performance specifications change: 4CH/module
5) Functional specifications: RTD Ni100-compliant and transformer isolation is provided
Transition to Q series
Remarks (Restrictions)
: Cable size is changed.
: Changed (4 modules are required when one A616TD and one
A60MXT(N) are used.)
: The number of occupied I/O points, I/O signals, and buffer memory
addresses are changed.
: Connector wiring and cable size are changed.
: Changed (2 modules are required when one A616TD and one
A60MXT(N) are used.)
: The number of occupied I/O points, I/O signals, and buffer memory
addresses are changed.
Q68TD-G-H02). Transformer isolation is provided between channels.
: Cable size is changed.
: Changed (2 modules are required.)
: The number of occupied I/O points, I/O signals, and buffer memory
addresses are changed.
: Cable size is changed.
: Changed (2 modules are required.)
: The number of occupied I/O points, I/O signals, and buffer memory
addresses are changed.
between channels.
: Connector wiring and cable size are changed.
: Not changed
: The number of occupied I/O points, I/O signals, and buffer memory
addresses are changed.
transformer isolation is provided between channels.
: Cable size is changed.
: Changed (2 modules are required.)
: The number of occupied I/O points, I/O signals, and buffer memory
addresses are changed.
: Cable size is changed.
: Changed (2 modules are required.)
: The number of occupied I/O points, I/O signals, and buffer memory
addresses are changed.
between channels.