4
TEMPERATURE INPUT MODULE REPLACEMENT

4.6.4 Buffer memory address comparison

Sequence program change is required as the assignment of buffer memory differs.
For details of the buffer memory and sequence program, refer to the RTD Input Module/Channel
Isolated RTD Input Module User's Manual.
A68RD3N
Address
Name
(decimal)
0
Conversion enable/disable specification
1
Averaging processing selection
2
CH1 Averaging time/count
3
CH2 Averaging time/count
4
CH3 Averaging time/count
5
CH4 Averaging time/count
6
CH5 Averaging time/count
7
CH6 Averaging time/count
8
CH7 Averaging time/count
9
CH8 Averaging time/count
10
CH1 Detected temperature value (16bit)
11
CH2 Detected temperature value (16bit)
12
CH3 Detected temperature value (16bit)
13
CH4 Detected temperature value (16bit)
14
CH5 Detected temperature value (16bit)
15
CH6 Detected temperature value (16bit)
16
CH7 Detected temperature value (16bit)
17
CH8 Detected temperature value (16bit)
18
CH1 Detected temperature value (L)
19
(32bit)
20
CH2 Detected temperature value (L)
21
(32bit)
22
CH3 Detected temperature value (L)
23
(32bit)
24
CH4 Detected temperature value (L)
25
(32bit)
26
CH5 Detected temperature value (L)
(32bit)
27
28
CH6 Detected temperature value (L)
29
(32bit)
30
CH7 Detected temperature value (L)
31
(32bit)
32
CH8 Detected temperature value (L)
33
(32bit)
34
Write data error code
35
Conversion completion flag
36
Specification of platinum RTD type
4
- 49
Address
Read/write
(decimal)
0
1
2
3
4
R/W
5
6
7
8
9
10
11
12
13
14
15
16
17
18
(H)
19
R
20
(H)
21
22
(H)
23
24
(H)
25
26
(H)
27
28
(H)
29
30
(H)
31
R
32
(H)
33
R/W
34
R
35
R/W
36
37
38
39
Q68RD3-G
Name
Conversion enable/disable setting
CH1 Time/count/moving average/time
constant setting
CH2 Time/count/moving average/time
constant setting
CH3 Time/count/moving average/time
constant setting
CH4 Time/count/moving average/time
constant setting
CH5 Time/count/moving average/time
constant setting
CH6 Time/count/moving average/time
constant setting
CH7 Time/count/moving average/time
constant setting
CH8 Time/count/moving average/time
constant setting
System area (Not used)
Conversion completion flag
CH1 Measured temperature value
CH2 Measured temperature value
CH3 Measured temperature value
CH4 Measured temperature value
CH5 Measured temperature value
CH6 Measured temperature value
CH7 Measured temperature value
CH8 Measured temperature value
Error code
Setting range 1 (Input type CH1-4)
Setting range 2 (Input type CH5-8)
Setting range 3 (Offset/gain setting)
System area (Not used)
Averaging processing selection (CH1-CH4)
Averaging processing selection (CH5-CH8)
Offset/gain setting mode (Offset
specification)
Offset/gain setting mode (Gain specification)
CH1 Offset temperature setting value
CH1 Gain temperature setting value
CH2 Offset temperature setting value
CH2 Gain temperature setting value
CH3 Offset temperature setting value
CH3 Gain temperature setting value
CH4 Offset temperature setting value
CH4 Gain temperature setting value
CH5 Offset temperature setting value
CH5 Gain temperature setting value
CH6 Offset temperature setting value
CH6 Gain temperature setting value
Read/write
R/W
-
R
-
R/W