Mitsubishi Electric MELSEC-A/QnA Series Handbook page 223

Table of Contents

Advertisement

5
MULTIPLEXER REPLACEMENT
-10 to 0 to +10VDC (Input resistance value: 1M)
0 to 20mADC (Input resistance value: 250)
Maximum resolution
Input
Analog input range
32 bits
0 to 10V
156.3µV
0 to 5V
78.2µV
1 to 5V
62.5µV
User range settings
Voltage
47.4µV
(Uni-polar)
-10 to 10V
156.3µV
User range settings
47.4µV
(Bi-polar)
0 to 20mA
312.5nA
4 to 20mA
250.0nA
Current
User range settings
151.6nA
(Uni-polar)
Reference accuracy
Temperature coefficient
Specific isolated area
Between the I/O terminal and
programmable controller power supply
Between analog channels
(I/O assignment: intelligent 16 points)
R1.25-3 (A solderless terminal with sleeve can not be used.)
Q64AD-GH
-
Digital
output value
16 bits
(32 bits)
312.6µV
156.4µV
0 to 64000
125.0µV
94.8µV
312.6µV
-64000 to 64000
94.8µV
625.0nA
500.0nA
0 to 64000
303.2nA
±
0.05%
Digital output value (32 bit)
Digital output value (16 bit)
±
71.4ppm/°C (0.00714%/°C)
±15V
±30mA
4 channels/module
-
Isolation
Dielectric withstand
method
voltage
Photocoupler
isolation
1780VrmsAC/3 cycles
(Altitude 2000m)
Transformer
isolation
16 points
18-point terminal block
2
0.3 to 0.75mm
0.89A
0.2kg
: Compatible,
Compatibility
-
Digital
output value
(16 bits)
0 to 32000
-32000 to 32000
0 to 32000
±
32 digits
±
16 digits
-
Insulation
resistance
500VDC,
10M
or more
×
×
×
: Partial change required, ×: Incompatible
Precautions for replacement
The minus current cannot be input.
Analog output voltage to the
A616AD
With A60MXR, equivalent or more
resolution value can be obtained
by setting at the analog inputs,
range of -10 up to 10V/high
resolution mode, and User range
while the analog inputs are used at
the range of -5 up to 5V on
Q64AD-GH.
When using a range of -20 up to
+20mA (with A60MXR), negative
current can not be converted with
Q64AD-GH.
Use conversion devices to convert
into a input range.
A60MXR is the accuracy in respect
to the full scale, and Q64AD-GH is
the accuracy in respect to
maximum digital output value.
Consider replacement with
multiple Q64AD-GH.
Q64AD-GH cannot set to 0 point
with I/O assignment.
Wiring change is required.
The recalculation of internal
current consumption [5VDC] is
required.
5
- 10

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec q series

Table of Contents