2
ANALOG INPUT MODULE REPLACEMENT
Between the I/O terminal and programmable controller power supply:
Between channels: transformer isolation
Between the I/O terminal and programmable controller power supply:
500VACrms, for 1 minute
Between analog input channels: 1000VACrms, for 1 minute
Between the I/O terminal and programmable controller power supply:
500VDC, 10M or more
Between analog input channels: 500VDC, 10M or more
(I/O assignment: intelligent 16 points)
Q68AD-G
10ms/channel
(Sampling cycle)
20ms
Voltage: ±15V
current: ±30mA
8 channels/module
Up to 50,000 times
transformer isolation
16 points
40-pin connector
2
Within 0.3mm
-
0.46A
0.16kg
: Compatible,
: Partial change required, ×: Incompatible
Compatibility
Precautions for replacement
I/O occupied points has changed to
16 points.
×
×
Wiring change is required.
×
The recalculation of internal current
consumption [5VDC] is required.