4
TEMPERATURE INPUT MODULE REPLACEMENT
*1
Restrictions on mountable slot position apply to the Q68TD-G-H01.
For details, refer to the user's manual for the Q68TD-G-H01/H02.
*2
Calculate the accuracy in the following method.
(Accuracy) = (Conversion accuracy) + (Temperature characteristics) × (Operating ambient temperature variation)
+ (Cold junction compensation accuracy)
An operating ambient temperature variation indicates a deviation of the operating ambient temperature from the 25±5°C
range.
*3
A measured temperature value is stored in the buffer memory at every 320ms/640ms, regardless of the number of
conversion enable channels.