2
ANALOG INPUT MODULE REPLACEMENT
Q68ADV
-10 to 10VDC
(Input resistance value: 1M)
-
(Normal resolution mode: -4096 to 4095,
High resolution mode: -12288 to 12287, -16384 to 16383)
Normal resolution mode
Analog input
Digital
range
output value
0 to 10V
0 to 5V
0 to 4000
1 to 5V
Voltage
-10 to 10V
-4000 to 4000
User range
settings
0 to 20mA
0 to 4000
4 to 20mA
Current
User range
-4000 to 4000
settings
Normal resolution mode
Ambient temperature
0 to 55°C
Analog input
With
range
temperature
temperature
drift
compensation
compensation
0 to 10V
-10 to
10V
0 to 5V
Voltage
1 to 5V
User
range
±0.3%
settings
(±12 digits)
(±16 digits)
0 to
20mA
4 to
Current
20mA
User
range
settings
0 to 20mADC
(Input resistance value: 250)
16-bit signed binary
Maximum
Digital
resolution
output value
2.5mV
0 to 16000
1.25mV
0 to 12000
1.0mV
2.5mV
-16000 to 16000
0.375mV
-12000 to 12000
5µA
0 to 12000
4µA
1.37µA
-12000 to 12000
High resolution mode
Ambient temperature
0 to 55°C
Ambient
Without
With
temperature
temperature
25±5°C
drift
drift
compensation
±0.3%
(±48 digits)
±0.4%
±0.1%
(±4 digits)
±0.3%
(±36 digits)
: Compatible,
Q68ADI
Compatibility Precautions for replacement
-
High resolution mode
Maximum
resolution
0.625mV
0.416mV
0.333mV
0.625mV
0.333mV
1.66µA
1.33µA
1.33µA
Ambient
Without
temperature
temperature
25±5°C
drift
compensation
±0.4%
±0.1%
(±64 digits)
(±16 digits)
±0.4%
±0.1%
(±48 digits)
(±12 digits)
: Partial change required, ×: Incompatible
The voltage/current cannot be
mixed for one module.
A616AD can set the data
format to [-2048 to 2047].
However, Q68ADV/I cannot
set. When using the
conversion data of Q68ADV/I
in [-2048 to 2047], convert with
sequence program.
When using A616AD in [-5 to +
5V] range, Q68ADV can obtain
equivalent resolution or more
than A616AD by setting in [-10
to 10V] range/high resolution
mode or user range.
When using A616AD in [-20 to
+20mA] range, use Q68ADI in
user range.
A616AD is the accuracy in
respect to the full scale, and
Q68ADV/I is the accuracy in
respect to maximum digital
output value.
2