POSITIONING MODULE REPLACEMENT
(2) Changed function from AD75P1-S3/P2-S3/P3-S3
In case of using the following functions with AD75P-S3, make sure that there is no operation problems
when converted to QD75PN/QD75DN.
Changed functions
1. The limit check of arc address is carried out only when a sub point is designated.
2. The software stroke limit check during speed control is carried out in the following cases:
• When the software stroke limit is applied to the current feed value with
• When the software stroke limit is applied to the machine feed value
3. If an attempt is made to change the current value but the designated address is out of the software stroke
Software stroke limit
function
4. Error code change
Current value changing M
1. An error occurs when the designated new current value is out of the software stroke limit range.
code function
2. The M code setting value is valid during the positioning data current value changing instruction.
1. An error occurs when the command frequency value calculated from the speed limit value exceeds the
Acceleration/deceleration
speed control
2. Only two-word type (1 to 8388608ms) can be used as the setting value for the acceleration/deceleration
1. "Peripheral side (emergency) stop" is deleted from the stop causes of Stop group 2 "sudden stop
Stop process and restart
after stop positioning
2. "Stop (QD75 peripheral)" is added to the stop causes of Stop group 3 "sudden stop selection".
operation stop
3. Error code 100 (Peripheral device stop during operation) is deleted.
4. "Programmable controller CPU error occurrence" is added to the stop causes of Stop group 2 Sudden stop
READY signal (X0)
Manual pulse generator
The No. of connectable manual pulse generator is changed from 1generator/1axis to 1generator/1 module.
operation
Axis operation status
"Step stopped" is changed to "Stopped" and "Step error occurring" is changed to "Error occurring".
• AD75P-S3:
Continuous path control
• QD75PN/QD75DN:
For the continuous path control, only the near pass function is available.
Near pass
Positioning address pass is not conducted.
2-axis interpolation
• 2-axis linear interpolation
The interpolation target axis can be randomly set with a positioning identifier.
• 2-axis fixed-feed
• Circular interpolation
7
- 9
It is not carried out when a center point is designated.
updated with
Pr.21
limit range, the attempt is considered as an error and the current value is not changed.
AD75P-S3:
There are 3 types of errors for each upper and lower stroke limit.
(error code 509 to 512)
QD75PN/QD75DN:
Errors for the software stroke upper limit are integrated in to error code 507.
Errors for the lower limit are integrated in to error code 508.
Error codes 509 to 512 are deleted.
maximum command frequency of the positioning module being used.
time.
selection".
"Test mode fault" in the stop causes of Stop group 3 "sudden stop selection" is changed to be in the stop
causes of Stop group 2 "sudden stop selection".
selection.
OFF
ON
If the reference axis operates in reverse direction, the control is internally changed into the continuous
positioning control. (restart after deceleration stop)
Even if the reference axis operates in reverse direction with interpolation, the control remains as the
continuous path control.
(In single-axis operation, the operation is the same as that of the AD75P-S3.)
Change description
Pr.14
AD75P-S3
Normal (READY)
Not READY/WDT error
and the current feed value is
QD75PN/QD75DN
Not READY/WDT error
Normal (READY)