Huawei NetCol5000-C030 User Manual page 97

In-row chilled water smart cooling product
Hide thumbs Also See for NetCol5000-C030:
Table of Contents

Advertisement

NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual
Menu
T/H
sensor
Issue 04 (2021-03-15)
Parameter
Description
In-cabinet
Set this parameter to
water overflow
Shutdown,
alarm action
Inactivity, Only
indoor fan running,
or Humidifier
stopped based on
site requirements.
Temperature
Cold aisle, Hot aisle,
and humidity
Return air, or Supply
control type
air can be set as
required. The
temperature and
humidity set points
correspond to the
selected control type
can be set.
Temperature
After the temperature
setpoint
and humidity control
type and the
temperature value
under this type are
set, the device
performs cooling or
heating based on the
settings.
Humidity
After the temperature
setpoint
and humidity control
type and the
humidity value under
this type are set, the
device performs
humidifying or
dehumidifying based
on the settings.
Copyright © Huawei Technologies Co., Ltd.
4 Power-On Commissioning
Setting Rule
Retain the default value.
● When the application
scenario is cold or hot
aisle containment, you
are advised to choose
Cold aisle if the cold
aisle T/H sensors are
configured, and choose
Supply air if the cold
aisle T/H sensors are
not configured.
● When the application
scenario is non-aisle
containment, you are
advised to choose
Return air, and choose
Cold aisle if the cold
aisle T/H sensors are
configured.
● Hot aisle is not
recommended.
Set this parameter as
required.
● Return air temperature:
26–35°C recommended
● Supply air temperature:
18–24°C recommended
● Cold aisle temperature:
18–24°C recommended
● Hot aisle temperature:
26–35°C recommended
Set this parameter as
required.
40%–60% RH
recommended
89