Huawei NetCol5000-C030 User Manual page 94

In-row chilled water smart cooling product
Hide thumbs Also See for NetCol5000-C030:
Table of Contents

Advertisement

NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual
Menu
Teamw
ork
Setting
s
System
Option
al Parts
Issue 04 (2021-03-15)
Parameter
Description
Teamwork
Set the assigned
group No.
teamwork control
number.
System address
Set the planned unit
address.
Teamwork
Indicates whether to
function
enable the teamwork
function. If no, the
unit operates
independently. If yes,
the unit operates in a
team with other
units.
Networking
Networking mode for
mode
the teamwork. The
networking mode set
on the screen must
be consistent with
the actual
networking mode.
Otherwise, the
teamwork control
function will be
unavailable.
Cold aisle
Cold aisle sensors can
sensor 1–5
be set to Enable or
Disable.
Hot aisle sensor
Hot aisle sensors can
1–5
be set to Enable or
Disable.
Copyright © Huawei Technologies Co., Ltd.
4 Power-On Commissioning
Setting Rule
The number of the
teamwork controlled
group, which is the same
for all the devices in the
group.
The addresses of units in
the same teamwork group
cannot be the same.
Set this parameter based
on the onsite device heat
distribution.
Networked over CAN or
MAC_CAN. CAN network
indicates teamwork control
over a CAN bus, MAC_CAN
network teamwork control
over an FE port.
If a T/H sensor outside the
cabinet is deployed in the
cold aisle, enable the T/H
sensor.
If a T/H sensor outside the
cabinet is deployed in the
hot aisle, enable the T/H
sensor.