Context
The parameters in this section are for reference only. Set actually parameter values
as required.
Procedure
Step 1 On the home screen, tap
Settings page, as shown in
Figure 4-6 Teamwork settings
Step 2 Set teamwork control parameters.
All teamwork control parameters can be set on the master smart cooling product.
Only Teamwork group No., Smart cooling product address, Enable teamwork
CAN resistor, Teamwork function and Networking mode can be set on slave
smart cooling products. Other parameters of the slave units will be modified by
the master unit synchronously.
Table 4-6 Teamwork settings
Paramete
r
Teamwork
group No.
System
address
Issue 04 (2021-03-15)
the smallest unit address is the master unit, and it cannot be changed. The
master unit collects, processes, and delivers group data.
Description
The number of the
teamwork controlled group,
which is the same for all
the devices in the group.
Smart cooling product
addresses should be
different from each other.
Copyright © Huawei Technologies Co., Ltd.
> Teamwork Settings to enter the Teamwork
Figure
4-6.
Table 4-6
describes how to set the parameters.
Setting Rule
Set the assigned
teamwork control
number.
Set the assigned unit
address.
4 Power-On Commissioning
Default
Value
1
NA
97