NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual
Item
Pipe and
cable routing
Air filter level
Net weight
(kg)
a: Rated working conditions are that the return air temperature is 37°C; the
return air relative humidity is 24%; the supply/return water temperatures are
10°C/15°C respectively; and the static pressure outside the smart cooling
product is 0 Pa.

2.10 Performance Curves

Figure 2-13
in proportion to the altitude when the NetCol5000-C works under rated power
and air flow.
Cooling Capacity Derating Coefficient Curve in Proportion to the Altitude
Figure 2-13 Cooling capacity derating coefficient curve in proportion to the
altitude
Cooling Capacity Curve in Proportion to the Glycol Solution Density
The cooling capacity is obtained by multiplying the glycol solution density by the
rated cooling capacity.
Issue 04 (2021-03-15)
NetCol5000-C030
Installed on a raised floor or base;
bottom pipe routing. Top pipe and
cable routing can also be
supported.
G4
● NetCol5000-C030H90D0: 162
● NetCol5000-C030H9HD0: 164
● NetCol5000-C030H9HE0: 164
and
Figure 2-14
NO TE
When the altitude is within 1000 m, the cooling capacity deviation is in the tolerance range
and can be ignored.
Copyright © Huawei Technologies Co., Ltd.
show the cooling capacity derating coefficient curve
2 Product Description
NetCol5000-C032
Installed on the raised
floor or base. It supports
underfloor piping and
overhead cabling.
G4
NetCol5000-C032H9HD0:
175
29