Signal Ports; Connecting The Teamwork Network Cable; Connecting The Fe Teamwork Network Cable - Huawei NetCol5000-C030 User Manual

In-row chilled water smart cooling product
Hide thumbs Also See for NetCol5000-C030:
Table of Contents

Advertisement

NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual
(9) Run/Alarm indicator
(11) Power indicator

3.12.4.2 Signal Ports

Figure 3-55 Signal ports
(1) Common alarm 2 (ALM_2 COM)
(3) Common alarm 1 (ALM_1 COM)
(5) External water sensor (Water -)
(7) Remote on/off (Remote COM)
(9) Smoke sensor (Smoke AI)

3.12.4.3 Connecting the Teamwork Network Cable

● Smart cooling products in a teamwork group must be of the same model.
● The default networking mode is CAN networking.
● The smart cooling product supports two teamwork networking modes: FE
teamwork networking and CAN teamwork networking (hand-in-hand).

3.12.4.3.1 Connecting the FE Teamwork Network Cable

Issue 04 (2021-03-15)
NO TICE
Copyright © Huawei Technologies Co., Ltd.
(10) DPT (used for connecting to the
differential pressure sensor)
(2) Common alarm 2 (ALM_2 NO)
(4) Common alarm 1 (ALM_1 NO)
(6) External water sensor (Water +)
(8) Remote on/off (Remote +)
(10) Smoke sensor (Smoke 12VDC)
3 Installation