Figure 3-38 Connecting the forcible drainpipe (rigid pipe connection)
Figure 3-39 Connecting the drainpipe (hose connection)
----End

3.8.3 (Optional) Connecting the Humidifier Water Inlet Pipe

Context
Procedure
Step 1 Install an adapter for the humidifier inlet water pipe. A sealing washer is
recommended.
● When plastic materials such as PA66 are used, the recommended torque is 5 N
m.
● When metal materials are used, the recommended torque is 10 N m. A sealing
washer must be used when an union is used.
Step 2 Clean the engineering pipe, connect the reserved humidifier water inlet pipe to the
engineering pipe, and wrap the pipe with thermal insulation foam.
Figure 3-40 Connecting the humidifier water inlet pipe
Issue 04 (2021-03-15)
A reducing valve must be installed if the inlet water pressure exceeds 0.7 MPa.
Appliance is intended to be permanently connected to the water mains and
not connected by a hose-set.