Huawei NetCol5000-C030 User Manual page 96

In-row chilled water smart cooling product
Hide thumbs Also See for NetCol5000-C030:
Table of Contents

Advertisement

NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual
Menu
Issue 04 (2021-03-15)
Parameter
Description
Humidifying
The humidifying
function
function can be set to
Enable, Disable, or
Enabled when active
power.
Dehumidifying
The dehumidifying
function
function can be set to
Enable, Disable, or
Enabled when active
power.
Floor water
Set this parameter to
overflow alarm
Shutdown,
action
Inactivity, Only
indoor fan running,
or Humidifier
stopped based on
site requirements.
Copyright © Huawei Technologies Co., Ltd.
4 Power-On Commissioning
Setting Rule
Enable indicates that the
electric humidifier will be
started when the ambient
humidity is lower than the
certain humidity range of
the humidity set point.
Disable indicates that the
electric humidifier will not
be started. Enabled when
active power indicates
that the electric humidifier
will be started when the
main power is active and
the ambient humidity is
lower than the certain
humidity range of the
humidity set point.
Enable indicates that the
dehumidification function
will be enabled when the
ambient humidity exceeds
the certain humidity range
of the humidity set point.
Disable indicates that the
dehumidification function
will not be enabled.
Enabled when active
power indicates that the
dehumidification function
will be enabled when the
main power is active and
the ambient humidity
exceeds the certain
humidity range of the
humidity set point.
Retain the default value.
88

Advertisement

Table of Contents
loading

This manual is also suitable for:

Netcol5000-c032Netcol5000-c065

Table of Contents