Teamwork Networking And Monitoring; Main Control Board Ports - Huawei NetCol5000-C030 User Manual

In-row chilled water smart cooling product
Hide thumbs Also See for NetCol5000-C030:
Table of Contents

Advertisement

NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual
Step 5 Check that the cable connections are secure.
Step 6 Reinstall the cover of the electric control box.
----End

3.12.4 Teamwork Networking and Monitoring

3.12.4.1 Main Control Board Ports

Figure 3-54 Main control board ports
(1) T/H_1 (T/H RS485 communications port)
(used for connecting to the external
temperature and humidity sensor)
(3) CAN_IN/CAN_OUT (used to connect CAN
teamwork and RS485 monitoring cascading
communications cables)
FE_IN/FE_OUT (used to connect FE teamwork
and smart module monitoring communications
cables)
(5) COM_OUT (RS485 communications port)
(used for connecting to the monitoring system)
(7) USB
Issue 04 (2021-03-15)
If there is a short circuit, remove the cable and reconnect it using the method
described in
Step
3.2. After verifying the connection, perform
If there is no short circuit, perform
If the cable connections are loose, fasten the connections.
If the cable connections are secure, the connection is complete.
Copyright © Huawei Technologies Co., Ltd.
Step
5.
(2) T/H_2 (T/H RS485 communications port)
(used for connecting to the external
temperature and humidity sensor)
(4) COM_IN (RS485 communications port)
(used for connecting to the monitoring system)
(6) FE (used for connecting to the monitoring
system)
(8) DP port
3 Installation
Step
5.
71