How Do I Calibrate A Sensor; How Do I Change The Password - Huawei NetCol5000-C030 User Manual

In-row chilled water smart cooling product
Hide thumbs Also See for NetCol5000-C030:
Table of Contents

Advertisement

NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual
Figure 7-14 Performance Maint screen
Step 2 Tap Clear in the row of a performance parameter to clear the runtime.
----End

7.1.11 How Do I Calibrate a Sensor?

Context
Calibrate a sensor if the displayed temperature or humidity on the sensor deviates
from the actual value. For example, if the return air temperature measured by
other temperature detection devices at the return air detection point is 20°C while
the value measured by the sensor is 22°C, the sensor has an error of 2°C, and the
calibration value should be set to –2°C.
Procedure
Step 1 On the home screen, choose Maint > Sensor Calibration.
Step 2 Fill the calibration value based on the measured error.
----End

7.1.12 How Do I Change the Password?

Prerequisites
Procedure
Step 1 On the home screen, choose Settings > User Settings to enter the User Settings
screen, as shown in
Issue 04 (2021-03-15)
If you need to change a password, log in as user admin or operator.
You can only change the password of the current user.
Figure
Copyright © Huawei Technologies Co., Ltd.
7-15.
7 FAQ
184