Check first when you have a trouble

5.5

Check first when you have a trouble

POINT
 If the cause is still unknown after every check, it is recommended to initialize the parameters (initial value) then
set the required parameter values and check again.
5.5.1

Motor does not start

Check
Points
Appropriate power supply voltage is not applied.
(Operation panel display is not provided.)
Main
Circuit
Motor is not connected properly.
The jumper across P/+ to P1 is disconnected.
Start signal is not input.
Both the forward and reverse rotation start signals (STF,
STR) are input simultaneously.
Speed command is zero.
AU signal is not ON when terminal 4 is used for speed
setting.
Output stop signal (MRS) or reset signal (RES) is ON.
(RUN LED on the operation panel flickers while MRS
signal is ON.)
Input
Signal
Jumper connector of sink - source is wrongly selected.
Voltage/current input switch is not correctly set for
analog input signal (0 to 5V/0 to 10V, 4 to 20mA).
was pressed.
(Operation panel indication is
Two-wire or three-wire type connection is wrong.
Servo-ON signal (SON) is assigned, but is not input.
Under position control, servo-ON signal (SON) or pre-
excitation signal (LX) is not input.
Under position control, position control sudden stop
signal (X87) is input.
280
Possible Cause
(PS).)
Countermeasures
Power ON moulded case circuit breaker (MCCB), an
earth leakage circuit breaker (ELB), or a magnetic
contactor (MC).
Check for the decreased input voltage, input phase loss,
and wiring.
Check the wiring between the drive unit and the motor.
Securely fit a jumper across P/+ to P1.
To use a DC reactor (FR-HEL) or Filterpack, remove the
jumper across the terminals P/+ and P1, then connect
the DC reactor or Filterpack.
Check the start command source, and input a start
signal.
PU operation mode:
External operation mode : STF/STR signal
Turn ON only one of the forward and reverse rotation
start signals (STF or STR).
If the STF and STR signals are turned ON
simultaneously in the initial setting, a stop command is
given.
Check the speed command source and enter a speed
command.
Turn ON the AU signal.
Turning ON the AU signal activates terminal 4 input.
Turn MRS or RES signal OFF.
Drive unit starts the operation with a given start
command and a speed command after turning OFF
MRS or RES signal.
Before turning OFF, ensure the safety.
Check that the control logic switchover jumper connector
is correctly installed.
If it is not installed correctly, input signal is not
recognized.
Set Pr.73, Pr.267, and a voltage/current input switch
correctly, then input an analog signal in accordance with
the setting.
During the External operation mode, check the method
of restarting from a
input stop from PU.
Check the connection.
Connect STOP signal when three-wire type is used.
Turn ON the SON signal.
Assign the SON signal or the LX signal to an input
terminal, and turn ON the signal.
Turn OFF the X87 signal.
Check the Pr.535 Position control terminal input selection
setting.
Refer
to
page
15
32
188
168
188
168
18
21
18
270
142
131
131
100