Mitsubishi Electric FR-E700EX Instruction Manual page 195

Sensorless servo drive unit, applied
Hide thumbs Also See for FR-E700EX:
Table of Contents

Advertisement

 When switching between the Network operation mode and External operation mode
1)Set Pr.79 to "0 (initial value), 2, 6 or 7". (At the Pr.79 setting of "7", the operation mode can be switched when the X12
(MRS) signal turns ON.)
2)Set "0 (initial value) or 1" in Pr.340 Communication startup mode selection.
3)Set "66" in any of Pr.178 to Pr.184 to assign the NET-PU operation switching signal (X66) to the terminal.
4)The operation mode changes to the Network operation mode when the X66 signal turns ON, or to the External
operation mode when the X66 signal turns OFF.
Pr.340
Pr.79
Setting
Setting
0 (initial value)
1
2
3, 4
0 (initial
6
value), 1
X12 (MRS)
ON
7
X12 (MRS)
OFF

PU operation mode is selected when Pr.550 NET mode operation command source selection = "0" (communication option command source) and the
communication option is not fitted.

PU operation mode is selected when the X16 signal is OFF. When the X65 signal has been assigned, the operation mode changes with the ON/OFF state
of the X65 signal.
REMARKS
 The priorities of Pr.79, Pr.340 and signals are Pr.79 > X12 > X66 > X65 > X16 > Pr.340.
NOTE
 Changing the terminal assignment using Pr.178 to Pr.184 (input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.15 Jog speed setting
Pr.4 to 6, Pr.24 to Pr.27, Pr.232 to Pr.239 Multi-speed operation
Pr.75 Reset selection/disconnected PU detection/PU stop selection
Pr.161 Speed setting/key lock operation selection
Pr.178 to Pr.184 (input terminal function selection)
Pr.190 to Pr.192 (output terminal function selection)
Pr.340 Communication startup mode selection
Pr.550 NET mode operation command source selection
Selection of operation mode and operation location
X66 Signal State
ON (NET)
NET operation mode
External operation mode
PU operation mode
NET operation mode
External operation mode Cannot be switched to PU operation mode
External/PU combined operation mode
NET operation mode
External operation mode
NET operation mode
External operation mode Output stop in External operation mode
External operation mode
Refer to page 119
Refer to page 256
Refer to page 138
Refer to page 144
Refer to page 194
Refer to page 195
OFF (External)
Fixed to PU operation mode
External/PU combined mode fixed
Operation mode can be switched with
operation continued
Forcibly switched to External operation
mode
Refer to page 117
Refer to page 178
Remarks
4
193