Mitsubishi Electric FR-E700EX Instruction Manual page 178

Sensorless servo drive unit, applied
Hide thumbs Also See for FR-E700EX:
Table of Contents

Advertisement

Speed setting by analog input (terminal 2, 4)
(b) Method to adjust any point without application of a voltage (current) across terminals 2 and 5 (4 and 5)
(To change from 4V (80%) to 5V (100%))
Operation
1.
Confirm the operation status indicator and
operation mode indicator
The drive unit should be at a stop.
The drive unit should be in the PU operation
mode. (Use
)
2.
Press
to choose the parameter setting
mode.
3.
Turn
until
4.
Press
to display
5.
Turn
until
Set to C4 Terminal 2 speed setting gain.
6.
Press
to display the analog voltage
(current) value (%).
7.
Turn
to set gain voltage (%).
"0V(0mA) is 0%, 10V(5V, 20mA) is 100%"
REMARKS
The current setting at the instant of turning
displayed. You can not check after performing
operation in step 7.
8.
Press
to set.
Turn
to read another parameter.
Press
Press
REMARKS
By pressing
You can not check after performing operation in step 7.
176
appears.
.
(
) appears.
Flicker...Parameter setting complete!!
to return to the
indication (step 4).
twice to show the next parameter (
after step 6, you can confirm the current speed setting bias/gain setting.
Display
PRM indicator is lit.
(The parameter number read previously appears.)
C0 to C7 setting
is enabled.
Terminal 2 input is
selected
Hz
A
Hz
A
is
Hz
A
Hz
A
(Adjustment completed)
).
Terminal 4 input is
selected
Analog voltage (current) value
(%) across terminals 2-5
(across terminals 4-5)
The gain speed is reached
when the analog voltage
(current) value across
terminals 2-5 (across terminals
4-5) is 100%.
Terminal 2 input is
Terminal 4 input is
selected
selected