Siemens CPU 948 Programming Manual page 480

Simatic s5 s5-155u
Table of Contents

Advertisement

Applications
FB 101 continued:
0037
:L
FY 249
0038
:L
FY 243
0039
:><F
003A
:JC
= EMPT
003B
:
003C RECV :L
KB 246
:JU
OB 204
003D
003E
:L
FY 248
003F
:JM
=OBER
0040
:L
FY 249
0041
:L
KB 0
0042
:><F
0043
:JC
=RECV
0044
:
0045 EMPT :L
FY 242
0046
:I
1
0047
:T
FY 242
0048
:L
KB 4
0049
:<F
004A
:JM = SRCH
004B
:L
KB 0
004C
:T
=ERWA
004D
:BEU
004E
:
004F ERWA :L
KB 16
0050 OBER :T
=ERWA
0051
:BE
10 - 76
Receiving capacity = number
of reserved
memory fields ?
SF OB:
"Receive a data field"
Abort if error/warning
if receiving capacity = 0
process next
link
Increment
link counter
All links
processed ?
Regular program end:
RLO = 0, ERWA = 0
Program end if error:
RLO = 1, ERWA contains
error/warning number
CPU 948 Programming Guide
C79000-G8576-C848-04