Siemens CPU 948 Programming Manual page 433

Simatic s5 s5-155u
Table of Contents

Advertisement

CPU 948 Programming Guide
C79000-G8576-C848-04
Cond.
code
byte
Table 10-4 continued:
68
The management data (queue management) of the
selected links are incorrect; set up the buffer in the
coordinator 923C again using the INITIALIZE function
(SEND, RECEIVE, SEND TEST, RECEIVE TEST).
69
The parameter "block ID" (SEND) or the block ID provided
by the sender (RECEIVE) is illegal. The following errors are
possible:
- The block ID is less than 1,
- the block ID is greater than 2.
70
The parameter "block number" (SEND) or the block number
supplied by the sender (RECEIVE) is illegal, since it is a data
block with a special significance. The following errors are
possible:
- If the block ID = 1 : DB 0, DB 1
- if the block ID = 2 : DX 0
71
The parameter "block number" (SEND) or the block number
provided by the sender (RECEIVE) is incorrect. The
specified data block does not exist.
72
The parameter "field number" (SEND) is incorrect.
The data block is too short or the field number too high.
73
The data block is not large enough to receive the data field
transmitted by the sender (RECEIVE).