Possible errors
Scan control word
CPU 948 Programming Guide
C79000-G8576-C848-04
OB 143: "Delay Single Cyclic Timed Interrupts" On/Off
If an error occurs, the system program sets the RLO to '1'.
The errors listed in the following table can occur. If an error occurs,
the system program enters the error ID listed below in ACCU-1-L.
Table 6-11
Error IDs of OB 143 in ACCU-1-L
ID
Meaning
8F01H
Illegal function no. in ACCU-2-L
8F02H
One of the reserved bits in ACCU 1 is '1'
1) the incorrect value is located in ACCU-2-L
• • The status of the control word can be scanned with the following
program sequence:
1. load function no. '2' or '3' in ACCU-2-L,
2. load value '0' in ACCU 1,
3. call OB 143,
4. read out ACCU 1.
1)
1)
6 - 37