Message Information - Toshiba TOSVERT VF-AS3 Instruction Manual

Industrial inverter (for 3-phase motors)
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

■ Message information

Message
display
A-01
A-02
A-05
ASIA
4
Atn
4
CHn
CLr
db
8
dbOn
9
E1
E2
E3
EASy
End
13
EOFF
Err1
EU
FAIL
FIrE
FJOG
13. Trip information and measures
English
V/f 5-point setting
When <Pt:V/f Pattern> = "7: V/f 5-point set-
error 1
ting", two or more from <vL>, <F190>,
<F192>, <F194>, <F196> and <F198> are
set to the same value other than 0.0 Hz.
V/f 5-point setting
Inclination of V/f is large.
error 2
Base frequency set-
Tries to run in frequency over 10 times of the
ting error
base frequency.
Setting for Asia
Setting for Asia is selected in the setup
menu.
During auto tuning
Auto-tuning in progress.
Setting for China
Setting for China is selected in the setup
menu.
Reset command
The following was operated after trip is
acceptable
occurring.
1) Pressed [STOP] key once.
2) Set the reset terminal ON.
(During trip resetting operation)
During DC braking
DC braking in progress.
During motor shaft
Motor shaft fixing in progress.
fixing
Panel display one
The display digit on the operation panel over-
digit overflow
flowed by one digit.
Panel display two
The display digit on the operation panel over-
digits overflow
flowed by two digits.
Panel display three
The display digit on the operation panel over-
digits overflow
flowed by three digits.
Easy mode
Switched to [Easy mode].
Last of data
The last data item in <History function>.
Emergency off com-
When a run command is other than the
mand acceptable
operation panel, [STOP/RESET] key was
pressed once.
Frequency point
The setting on point 1 and point 2 of the fre-
setting error
quency command is close.
Setting for Europe
Setting for Europe is selected in the setup
menu.
Password failure
Entered number in <F739: Password verifi-
cation> does not match <F738: Password
setting>.
During Fire speed
Fire speed run/Forced run is in progress.
run/Forced run
("FIrE" and the output frequency are alter-
nately displayed)
Fwd JOG
Forward jog run in progress.
Description
Set different value on each parameter.
Set V/f 5-point and <vLv>/<vL> for the V/f
inclination to be gentle.
• Check that the base frequency setting is
• Operate in frequency within 10 times of the
-
A message that indicates auto-tuning in
progress. No problem if the message disap-
pears after several seconds.
-
Reset is performed with the following opera-
tion.
1) Press [STOP] key again.
2) Set the reset terminal OFF.
-
A message indicates the motor fixing control
in progress. When standby is turned OFF, the
control stops.
-
-
-
-
-
To apply emergency off, press [STOP] key
again.
If emergency off does not occur, press other
keys.
Set apart point 1 and point 2 of the frequency
command.
-
-
A message indicates fire speed run/forced
run in progress. It stops when turning the
power OFF.
-
13-10
E6582062
Remarks
correct. <vL: Base frequency 1>, etc.
base frequency.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents