6. 36 Store cumulative power

<F748: Cumulative power save>
<F749: Cumulative power unit>
■ Function
At the main power off, the integrating wattmeter can be stored, or the unit of the integral output
power can be selected.
■ Parameter setting
Title
Parameter name
F748
Cumulative power save
F749
Cumulative power unit
*1
Depending on capacity. For details, refer to [11. 6].
• The integrating wattmeter display can be cleared by the signal to the input terminal. Assign "74:
Memo
Cumulative power monitor clear" to the unused input terminal. For details, refer to [7. 2. 1].
• How to operate the operation panel -> Refer to [3. 1. 1].
• How to switch display mode on the operation panel -> Refer to [3. 1. 2].
Reference
• Procedure to change parameter setting -> Refer to [4. 2. 3]
• Details on operation by external signals -> Refer to [Chapter 7].
F748 : Cumulative power save
0: Disabled
1: Enabled
Adjustment range
0: Disabled
1: Enabled
0: 1.0=1 kWh
1: 1.0=10 kWh
2: 1.0=100 kWh
3: 1.0=1000 kWh
4: 1.0=10000 kWh
5: 1.0=100000 kWh
6-179
E6582062
STOP
0.0Hz
14:16
Default setting
0
*1
6. [Advanced] How to use parameters
3
4
6
9