Operation Panel Female Connector; Usb-Minib Connector; Rs485 Communication Connector 1; Indicators For Communication - Toshiba TOSVERT VF-AS3 Instruction Manual

Industrial inverter (for 3-phase motors)
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

• Operation panel female connector

For remote control, connect the operation panel to this female connector with a cable. To mount the
operation panel on the cabinet, use the door mount kit (optional).

• USB-miniB connector

Used only by manufacturer.
• Slot for battery
1
A lithium battery is inserted to this slot for internal real time clock of the operation panel (equipped as
standard at the time of shipping). For how to replace the battery, please consult your Toshiba
distributor. For the time of battery replacement, refer to [14. 2. 3].

■ RS485 communication connector 1

Normally, this connector is used for connection of the operation panel.
For remote control, connect the operation panel with an exclusive extension cable (optional).

■ Indicators for communication

The upper three LEDs indicate the operation status, trip status, and STO (Safe Torque Off)
respectively from the top.
STATUS (Green LED)
- On: Stopped
- Fast blinking: Run command ON, frequency command 0
- Slow blinking: During run
- Off: Power OFF
9
(Red LED)
- Blinking: A trip has occurred
- Off: In normal condition
ASF (Yellow LED)
- On: STO
- Off: In normal condition
Other seven LEDs indicate the communication status.
1. Read first
1-10
E6582062

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents