6. 23. 2

Setting PM motor parameters

<F400: Offline auto-tuning>
<F402: Automatic torque boost>
<F405: Motor rated capacity>
<F415: Motor rated current>
<F417: Motor rated speed>
<F459: Load inertia ratio>
<F462: Speed reference filter coefficient 1>
<F465: Speed reference filter coefficient 2>
<F912: PM q-axis inductance>
<F913: PM d-axis inductance>
<F915: PM control method>
■ Function
To select PM motor control with <Pt: V/f Pattern>, you must set motor parameters (auto-tuning).
There are three setting methods.
• Set <Pt> and <F400: Offline auto-tuning> individually.
• Set <Pt> and <F400> individually. Perform an auto-tuning after calculating the motor parameter
automatically (available with motor not connected).
• Set <Pt> and set the motor parameter manually.
• To set <Pt: V/f Pattern> to "6: PM motor control", check the motor name plate and set the
following parameters first.
 - <vL: Base frequency 1> (Rated frequency): calculate from back EMF
 - <vLv: Base frequency voltage 1> (Rated voltage): calculate from back EMF
 - <F405: Motor rated capacity>
 - <F415: Motor rated current>
Important
 - <F417: Motor rated speed>
 - <F912: PM q-axis inductance>
 - <F913: PM d-axis inductance>

■ Setting method 1: Set auto-tuning

Set PM motor control and auto-tuning individually.
First, set <Pt: V/f Pattern> to "6: PM motor control". For details of setting methods, refer to [5. 2. 4].
Next, perform offline auto-tuning.
F912 : PM q-axis inductance
Min: 0.01
X1000
6-89
E6582062
STOP
0.0Hz
13:40
10.00
mH
Max: 650.00