■ Setting example of <F302: Regenerative power ride-through> = "1"
1) When the power supply is shut off
4
* Available time to continue the operation varies by the mechanical inertia or load condition.
4
Perform verification test when using this function.
* Using retry function at the same time enables to automatically restart without failure stop.
6
When the power supply is shut off during deceleration stop, the regenerative power ride-
through does not function.
2) When a momentary power failure occurs
9
When a momentary power failure occurs during deceleration stop, the regenerative power ride-
through does not function.
6. [Advanced] How to use parameters
Input power
DC voltage
inside inverter
Motor speed
Approx. 100 ms to 10 s
Input power
DC voltage
inside inverter
Motor speed
Regenerative power ridethrough control
Coasting
Ridethrough control
Normal acceleration
6-56