How to use parameters
Frequently set parameters include default 10 parameters in [Easy mode] and basic parameters.
This chapter describes these parameters.
5. 1
Settings of main parameters
This section describes how to select run and frequency commands required for operating the motor, how
to limit the output frequency, how to set acceleration/deceleration time, how to set the electronic thermal
for motor protection, and how to adjust the meter.
5. 1. 1
Selecting how to input run and frequency
commands
(1)
Selecting how to input run/stop
<CMOd: Run command select>
Basic parameter
■ Function
Select where to input a run command to the inverter.
■ Parameter setting
Title
CMOd
Run command select
■ Selecting a setting value
0: Terminal
Run/stop the inverter with an external ON/OFF signal.
For how to set terminals and parameters to be used, refer to [4. 4].
Easy mode
Parameter name
0: Terminal
1: Operation panel, Extension panel
2: Embedded Ethernet
3: RS485 communication (connector 1)
4: RS485 communication (connector 2)
5: Communication option
5-1
STOP
CMOd :Run command select
0: Terminal
1: Operation panel,Ext panel
2: Embedded Ethernet
3: RS485 com (connector 1)
4: RS485 com (connector 2)
Adjustment range
5. [Fundamental operation] How to use parameters