Fundamental Operation: How To Use Parameters; Settings Of Main Parameters; Selecting How To Input Run And Frequency Commands; Selecting How To Input Run/Stop - Toshiba TOSVERT VF-AS3 Instruction Manual

Industrial inverter (for 3-phase motors)
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

5
[Fundamental operation]
How to use parameters
Frequently set parameters include default 10 parameters in [Easy mode] and basic parameters.
This chapter describes these parameters.
5. 1

Settings of main parameters

This section describes how to select run and frequency commands required for operating the motor, how
to limit the output frequency, how to set acceleration/deceleration time, how to set the electronic thermal
for motor protection, and how to adjust the meter.
5. 1. 1
Selecting how to input run and frequency
commands
(1)

Selecting how to input run/stop

<CMOd: Run command select>
Basic parameter
■ Function
Select where to input a run command to the inverter.
■ Parameter setting
Title
CMOd
Run command select
■ Selecting a setting value
0: Terminal
Run/stop the inverter with an external ON/OFF signal.
For how to set terminals and parameters to be used, refer to [4. 4].
Easy mode
Parameter name
0: Terminal
1: Operation panel, Extension panel
2: Embedded Ethernet
3: RS485 communication (connector 1)
4: RS485 communication (connector 2)
5: Communication option
5-1
STOP
CMOd :Run command select
0: Terminal
1: Operation panel,Ext panel
2: Embedded Ethernet
3: RS485 com (connector 1)
4: RS485 com (connector 2)
Adjustment range
5. [Fundamental operation] How to use parameters
I
II
III
1
2
3
4
5
6
7
0.0Hz
15:06
8
9
10
11
12
13
Default
setting
14
0
15
16
17
18

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents