• Note that a higher value of <250: DC braking frequency> will cause a command indicating the
sudden stop of the motor from a high rotation state. A trip may occur depending on a load
condition.
Important
• When <F255: 0Hz command select at stop> is set to "1", the inverter outputs a 0 Hz command
instead of applying the following DC braking.
DC braking with a command from the terminal or communication (input terminal function "22"/
Memo
"23", communication command)
Emergency DC braking of DC braking emergency stop (<F603: Emergency off stop pattern> =
"2") when the DC braking stop of the jog stop pattern is specified (<F261: Jog stop select> =
"2")
• How to operate the operation panel -> Refer to [3. 1. 1].
• How to switch display mode on the operation panel -> Refer to [3. 1. 2].
Reference
• Procedure to change parameter setting -> Refer to [4. 2. 3]
• Details on operation by external signals -> Refer to [Chapter 7].