Function Parameter Index Reference

5.57 SPS Function Block

Description
The SPS label stands for Master Setpoint Scheduler. This block is part of the Setpoint Scheduler
category. It looks like this graphically on the Control Builder.
Dynamic Contained Parameters:
Parameter
Index
status
0
save_req
1
sta_req
2
pgm_req
3
seg_req
4
soaksp [8]
5-12
duration
13
PV [8]
14-21
adv_req
22
106

Table 5-74 SPS Dynamic Contained Parameters

Type
Use
R/W
REAL
C
R
REAL
C
R/W
REAL
C
R/W
REAL
C
R/W
REAL
C
R/W
REAL
C
R
REAL
C
R
REAL
C
R
BOOL
C
R/W
RS232 Communications Reference Manual
Description
block status
save current program request mailbox
state change request
program change request
segment change request
soak setpoint (eu)
segment duration (minutes/hours)
value of PV being controlled by SP program
segment advance request (leading edge)
8/99