Table 5-19 Carb Static Configuration Parameters - Honeywell UMC800 Reference Manual

Rs232 communications
Hide thumbs Also See for UMC800:
Table of Contents

Advertisement

Function Parameter Index Reference
FFV
19
TRV
20
TRC
21
BCI
23
BIAS
24
TEMP
26
%CO
27
Static Configuration Parameters:
Parameter
Index
GAIN
0
RATE
1
RESET
2
pv_hi
4
pv_lo
5
sp_hi_lim
11
sp_lo_lim
12
outhilim
14
outlolim
15
failsafe
16
al_sp[4]
17-20
al_hyst
25
man_reset
26
FUZZY
28
TUNESET2
29
GAIN2
30
RATE2
31
RESET2
32
use_propband
33
54
REAL
I
R
REAL
I
R
BOOL
I
R
REAL
I
R
REAL
I
R
REAL
I
R
REAL
I
R

Table 5-19 CARB Static Configuration Parameters

Type
Description
REAL
proportional gain, 0.1 to 1000 or proportional band, 0.1% to 1000%
[Tune Set 1]
REAL
derivative time, 0 or 0.1 to 10 (minutes) [Tune Set 1]
REAL
integration time, 0 or 0.02 to 50 (minutes) or repeats per minute, 0 or
0.02 to 50 (repeats) [Tune Set 1]
REAL
pv High Range value –99999 to 99999 (default 100)
REAL
pv Low Range value –99999 to 99999 (default 0)
REAL
set point high limit, -99999 to 99999 (default 100)
REAL
set point low limit, -99999 to 99999 (default 0)
REAL
output high limit, -5 to 105
REAL
output low limit, -5 to 105
REAL
failsafe output value, -5 to 105, (default 0)
REAL
alarm set points al1spl, al1sp2, al2spl, al2sp2, -99999 to 99999
(default 0)
REAL
alarm hysterysis 0 to 5 (%)
REAL
Manual Reset, -100 to 100 (in % output) (default 0) [used for both
tune sets]
BOOL
ON enables fuzzy logic overshoot suppression (default OFF)
BOOL
Use tune set 2 (default OFF)
REAL
proportional gain, 0.1 to 1000 or proportional band, 0.1% to 1000%
[Tune Set 2]
REAL
derivative time, 0 or 0.1 to 10 (minutes) [Tune Set 2]
REAL
integration time, 0 or 0.02 to 50 (minutes) or repeats per minute, 0 or
50 to 0.02 (repeats) [Tune Set 2]
BOOL
Use Gain (0) or Proportional Band (1)
RS232 Communications Reference Manual
Feed Forward Value (%)
Output Track Value (%)
Output Track Command {OFF, ON}
Back Calculation Input (%)
Remote bias value for ratio PID
Temperature input (°F or °C per USE_METRIC)
Percent carbon monoxide
8/99

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rs232

Table of Contents