Static Configuration Values:
Parameter
Index
pv_hi
0
pv_lo
1
outhilim
5
outlolim
6
failsafe
7
al_sp[4]
8-11
al_hyst
16
8/99
Table 5-13 AMB Static Configuration Values
Type
Description
REAL
pv High Range value -5 to 105%
REAL
pv Low Range value –5 to 105%
REAL
output high limit, -5 to 105
REAL
output low limit, -5 to 105
REAL
failsafe output value, -5 to 105, (default 0)
REAL
alarm set points al1spl, al1sp2, al2spl, al2sp2, -99999 to 99999
(default 0)
REAL
alarm hysterysis 0 to 5 (%)
RS232 Communications Reference Manual
Function Parameter Index Reference
47