AQ25A SERIES PROGRAMMABLE BOILER CONTROL PANELS
Installer Menu Structure
To display the Installer Menu, go to the Home Page, press and hold the OK button for 3 seconds until the message INSTALLER MODE –
ARE YOU SURE? displays. Select YES and press the OK button. Fig. 25 and Fig. 26 on page 39 illustrate all possible Installer Menu
selections.
INSTALLER MODE
INSTALLER MODE
ARE YOU SURE?
NO
YES
INSTALLER MENU
EQUIPMENT SETUP
TEST AND PURGE
EXIT INSTALLER
1
THE
SYMBOLS INDICATE ADDITIONAL SELECTIONS ARE POSSIBLE.
THE FACTORY DEFAULT VALUES ARE SHOWN.
A VALUE OF "- -" INDICATES THE ITEM IS DISABLED OR NOT USED.
2
TEMPERATURE VALUES ARE SHOWN IN DEGREES FAHRENHEIT,
WHICH IS THE FACTORY DEFAULT TEMPERATURE UNIT.
3
SOME ITEMS DISPLAY BASED ON PRIOR SELECTIONS.
FOR EXAMPLE, IF DHW PRIO = YES, THEN THE PRIO. OVER
SELECTION DISPLAYS.
4
THE ENVIRACOM SUB-MENU IS NOT USED.
69-2119—02
EQUIPMENT SETUP
BOILER SETTING
BOILER OPERATION
10V MOD. SELECT
DOMESTIC HOT WATER
ZONING
AUXILIARY I/O
A/C SETTINGS
A/C EQUIP CONFIG
STATISTICS
ENVIRACOM
SAVE/RESTORE
Fig. 25. Installer Menu Structure. – Equipment Setup.
38
1
BOILER SETTING
HIGH LIMIT:
190
2
LOW LIMIT:
150
BOILER DIFF:
AUTO
W.W.S.D.:
70
MIN.RETURN:
140
BOILER OPERATION
CYCLES/HOUR:
4
FIRE DELAY:
0:10
PURGE TIME:
0:30
EXERCISE:
YES
FREEZE PROT:
YES
10V MOD. SELECT
10V MOD:
0-10V
USAGE:
NONE
DOMESTIC HOT WATER
DHW:
ENABLE
DHW PRIO.:
NO
3
PRIO.OVER.:
YES
DHW DEVICE:
PUMP
DHW VLV.OP:
15
DHW PURGE:
YES
DHW SENSOR:
NO
DHW SETPOINT:
140
DHW DIFF:
20
DHW VACANCY:
45
ZONING
HT DMND PRIO:
NO
PRIO.OVER.:
YES
ZONING VALVES
TIME TO OPEN:
15
AUXILIARY I/O
AUX.IN:
SETBACK
AUX.OUT:
BOILER
AUX.PUMP:
BOILER
A/C SETTINGS
CYCLES/HOUR:
4
MIN.OFF TIME:
5M
C.W.S.D:
65
FAN MODE:
AUTO
A/C EQUIP CONFIG
ZONE:
A-1
A/C UNIT:
1
COOLING:
ENABLE
STATISTICS
LAST DATA RESET: 2000 JAN 01
RESET ALL DATA:
ARE YOU SURE?
NO
YES
BOILER FIRE ACTIV:
0H
BOILER PUMP ACTIV:
0H
DHW PUMP ACTIV:
0H
AUX PUMP ACTIV:
0H
AUX OUT ACTIV:
0H
ZONE
A-1
ACTIV:
0H
4
ENVIRACOM
MODULES ID:
0
SAVE/RESTORE
SAVE SETUP
RESTORE FACTORY
RESTORE SETUP
M27771