Installer Programming Menu

The Installer Menu allows you to set up and modify system
settings that typically would be adjusted by a trained installer.
These include settings such as mixing temperatures limits,
injection, and valve operation.
System statistics, testing, and purging are also available from
the Installer Menu.
Illustrations of the complete Installer Menu begin on page 19.
Menu Option
MIXING
MIX HIGH TEMP: - -
MIX LOW TEMP: - -
RESET:
DESIGN TEMP:
10V MOD:
INJECT.:
MIX.VLV:
VLV OPEN TIME: 5 to 230 seconds
VLV ACTION:
- EXIT -
PRI/SEC
ALL PRI
ALL SEC
B-01:
...
D-16:
- EXIT -
Table 3. Installer Menu.
EQUIPMENT SETUP
Range
Settings that the AQ254 uses for Secondary loop operation
80°F to 210°F (27°C to 99°C)
35°F to 150°F (2°C to 66°C)
AUTO / OUTDOOR / LOAD /
NONE
- -
70°F to 210°F (21°C to 99°C)
DISABLE /
0V to 10V /
2V to 10V
ENABLE / DISABLE
DISABLE / ENABLE
DIRECT / REVERSE
n/a
Identifies the heating water loop that each space heating zone is supplied by: the primary
boiler loop (PRI) or the secondary mixed loop (SEC).
Displays the PRI/SEC sub-menu with the following selections for all or individual zones:
n/a
n/a
SEC / PRI
n/a
AQ25400B "ADD-A-TEMPERATURE" EXPANSION CONTROL PANEL
To access the Installer Menu, press and hold the OK button for
3 seconds.
NOTE: To exit Installer Mode, select the Installer Exit menu
option.
Factory
Default
140°F
The maximum temperature that the control can use as
(60°C)
a target for the secondary loop supply water. The MIX
HIGH TEMP cannot be set below the MIX LOW
TEMP setting.
• "- -" means Off (not used).
95°F
The minimum temperature that the control can use as
(35°C)
a target for the secondary loop supply water. The MIX
LOW TEMP cannot be set above the MIX HIGH
TEMP setting.
• "- -" means Off (not used).
AUTO
Selects the calculation method (algorithm) that the
control uses to set the target temperature for the
secondary loop supply water.
AUTO option applies the same reset method selected
for the main AQ2000 Series Control Panel.
120°F
The supply water temperature required in the mixed
(49°C)
temperature SECondary loop when the outdoor
temperature is at the OUTDOOR LOW temperature.
• "- -" means Off (not used).
DISABLE
Produces voltage on the 10 Vdc low voltage terminals
(6 and 7) according to the setting chosen.
ENABLE
DISABLE
160
Available only when MIX.VLV = ENABLE
(seconds)
DIRECT
Available only when MIX.VLV = ENABLE
n/a
Exits this sub-menu and returns to the Installer menu.
n/a
Applicable only to the 16 zones of this AQ254 group
of zones (B, C, or D).
n/a
Applicable only to the 16 zones of this AQ254 group
of zones (B, C, or D).
SEC
Individual zone selection:
B-01: PRI/SEC
B-02: PRI/SEC
...
D-16: PRI/SEC
n/a
Exits this sub-menu and returns to the Installer menu.
15
Description
69-1987—02