Honeywell AQ25A Series Technical Reference Booklet page 162

Programmable boiler control panels
Hide thumbs Also See for AQ25A Series:
Table of Contents

Advertisement

AQ25400B "ADD-A-TEMPERATURE" EXPANSION CONTROL PANEL
LCD Display Navigation
This section describes how the keypad is used to navigate the
LCD display and menus.
The LCD displays up to three lines of text at a time. For menus
with more than three lines, use the up and down buttons (
v) to scroll through the menu options. As the menu is scrolled
up or down, the indicator arrow (←) shows which menu item is
active.
1. If the active menu item is part of a list of predefined
options (e.g., AUX.PUMP operation), press the OK but-
ton to edit this value (the word EDIT displays on the top
right portion of the AQ254 LCD screen) and then press
either the "-"or "+" button to scroll through the available
options. With the indicator arrow (←) beside the chosen
option, press the OK button again to accept this value,
exit EDIT mode, and return to the previous menu. The
option's value is automatically saved upon exiting EDIT
mode.
2. If the active menu item requires you to define a value
(e.g. a setpoint), position the indicator arrow beside the
menu item and press the OK button to edit this value (the
word EDIT displays on the top right portion of the AQ254
LCD screen) and then press either the "-"or "+" button to
change the value for the menu item until the desired
value is shown. Press the OK button again to accept this
value and return to the previous menu. Again, the
option's value is automatically saved upon exiting EDIT
mode.
3. If the active menu item leads to a further sub-menu,
pressing the OK displays that sub-menu. Scroll through
this sub-menu to position the indicator arrow (←) beside
the menu item to be reviewed or modified. Press the OK
button to edit this value (the word "EDIT" displays on the
top right portion of the AQ254 LCD screen). Choose one
of the options provided or input the desired value for the
menu item. Press the OK button again and your selec-
tion is saved.
4. To define or modify another item within the same menu,
scroll the UP and DOWN buttons (
tor arrow (←) is beside the desired option and repeat
Steps 1 through 3.
To move back (up) one level within a menu, scroll to the bottom
of the current menu list and – with the active indicator arrow
(←) beside the EXIT option, press the OK button.
To leave INSTALLER MODE and return to the Home Page
display screen, press and hold the OK button for 3 seconds
from any menu location within the INSTALLER menu.
69-1987—02
HOME PAGE DISPLAY
The Home Page is the default view displayed on the AQ254
Control Panel's LCD screen (refer to "Home Page and System
Status Page" on page 14 in the "Appendix" ).
The Home Page together with the System Status Page provide
or
^
a service contractor extensive diagnostic information for
troubleshooting the installation.
Programming the AQ254
Program the AQ254 by using the keypad and LCD display to
select parameters from the Installer menu. Refer to Fig. 7 on
page 9 for an illustration of the LCD screen and keypad.
NOTE: The figures in "Installer Menu Structure" on page 19
When a new AQ2000 component is connected on the
AQUATROL network, it is seamlessly integrated in the system
after a few seconds. If one or more components are
disconnected or stop providing data to the network, a message
will appear on the System Status page of the AQ254's LCD of
the main AQ2000 Control Panel until the fault is corrected.
System Status Page
The System Status Page is intended for use by the building
owner to view the system state and status.
NOTE: If there are any problems with the system's operation,
Refer to Table 2 on page 14 in the "Appendix" for all of the
possible status messages for the AQ254 Expansion Control
Panel, the factory default values and permissible ranges for
each option, and a brief description of each setting.
or v) until the indica-
^
Installer Menu
The Installer Menu is used to:
— Set up and modify the Loop and Mixing settings.
— Access the Test and Purge functions to facilitate quick and
TO ACCESS THE INSTALLER MENU:
Press and hold the OK button for 3 seconds.
Refer to Table 3 on page 15 in the "Appendix" for all of the
Installer Menu options for the Control Panel, the factory default
values and permissible ranges for each option, and a brief
description of how each setting affects the AQ254's operation.
10
provide a graphical layout of the AQ254's Installer
menu.
the AQ254 displays error codes on the System Status
Page display of the LCD panel. For details on these,
refer to "Troubleshooting" on page 13.
simple commissioning of the system.